WONACH SUCHST DU?
If the Cv value determines how much work the valve can do, then the leakage class (Leakage Class) and rangeability (Rangeability) determine the "quality of the work" the valve performs.

Leakage Class is the lower limit of performance: How tightly can the valve close?
Rangeability is the upper limit of performance: How wide can the valve adjust?
Many field incidents happen not because the valve cannot pass the flow, but because the valve cannot close properly (causing high-pressure gas leaks, material waste) or cannot adjust properly (causing instability at low flow and saturation at high flow).
In this article, we will explain these two key indicators that determine the "level" of a valve's performance.
01 Leakage Class: The Art of Closing the Valve
There is no absolute "zero leakage" in the world. Even metal atoms have gaps between them.
The industry standard followed is ANSI/FCI 70-2 (corresponding to IEC 60534-4). This standard divides leakage into 6 classes.
Here’s a detailed explanation of the commonly used classes:
Class IV: The Standard for Metal Hard Seal
Class V: A Tough Step to Cross
Class VI: The World of Soft Seals
💡 Selection Pitfall:
Do not blindly pursue Class VI. If you are working with high-temperature and high-pressure steam and demand Class VI, manufacturers will only be able to provide expensive special metal structures, leading to skyrocketing costs and uncertain service life. Typically, Class IV is sufficient for control valves.
02 Rangeability: Ideal vs. Reality
Rangeability, also known as Turndown Ratio, is defined as:
The ratio between the maximum controllable flow and the minimum controllable flow of the valve.

Why the "100:1" on samples is misleading:
The rangeability indicated on samples is called Inherent Rangeability.
But in the field, we are dealing with Installed Rangeability.
Remember the valve authority, S?
Pipe resistance will "eat up" the pressure difference of the valve
What does this mean?
It means that when the flow rate drops to 20%, the valve may already be near its closed position, becoming unstable.
✅ Engineering Rule:
Do not trust sample data blindly. In systems with low S values, the installed rangeability must be calculated. If the actual flow range is wide (e.g., minimal flow during startup, maximal flow during normal operation), one valve alone might not be sufficient. A "split range" solution, using multiple valves in parallel, might be needed.
Contact us now for more info of control valve: info@geko-union.com